Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
15.8 ESP-002
HEAT DISSIPATION DATA SHEET
Manufacturer: _________________________ Equipment: ____________________________ Date: _________________
List each active
Component in the system:
POWER
(Watts)
1
# of Units
(Count)
HEAT DISSIPATION
Per Unit (Watts)
HEAT DISSIPATION
TOTAL (Watts)
Description/Part/Card Number List 1 Drain
A: Max
3
Possible
B: AT&T
4
Design
C: Max
5
Possible
D: Nominal
6
AT&T Design
7
(A ) X (C) =
8
(B ) X (D) =
TOTAL WATTS FOR SYSTEM – REQUIRED FOR ALL
SUBMISSIONS
Airflow path design: – REQUIRED FOR ALL SUBMISSIONS
Are equipment air flow path(s) only front (intake) to rear (exhaust) (FX – RX) ? Yes _____
No _______
If No:
• Specify Path(s) ________________ _________________ ________________
• Attach a diagram depicting each of the path(s) & Specify direction of each of the flow(s)
Notes:
1) At no time shall Maximum Heat Dissipation be larger than List 1 Power Drain
2) Where possible, heat dissipation measurements should be measured rather than calculated.
• If the heat dissipation measurement is measured, follow the entry with a hyphen and the letter “M” for
measured
• If the heat dissipation measurement is calculated, follow the entry with a hyphen and the letter “C” for
calculated
• Examples: Measured = 4,000 – M or Calculated = 3,500 – C
• The “M” or “C” shall be included for each heat dissipation measurement entry
3) A: Maximum possible is the total number of units that may be deployed in a system by engineering design
4) B: AT&T design is the total number of units that AT&T will typically deploys in a system.
• If the typical AT&T units deployed are unavailable, indicate the maximum number followed by a hyphen
and the letter “U” for unknown. (e.g. 4-U)
Copyright ©2014, AT&T . All Rights Reserved.