Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
Outside Plant (OSP/CELL-SITE) – Outside plant part of the network. Typically network
locations between the inside of Network Equipment Space buildings and Customer
Premises Antenna locations. OSP/CELL-SITE equipment shall be Carrier Grade.
Most of World (MoW) - Equipment Deployed Outside the United States:
Equipment Deployed Outside the United States will require verification of compliance to
ATT-TP-76200/ATT-TP76450 per Appendix A and completed MoW Letter of Attestation
per Section 16 Form 16.12.
AT&T Test Laboratory – the primary purposes of lab entry requirements for equipment
under test are to ensure the safety of personnel and property. It is the objective of this
requirement that verification of compliance to industry safety standards be provided for
equipment prior to lab entry. However, due to needs of the business and the fact that the
lab is staffed by personnel trained to work with prototype equipment, there are times
when it may be necessary for AT&T to allow equipment into its lab that has not been
verified in compliance to safety standards. In those cases it is incumbent upon the
manufacturer to assure the equipment is safe to operate. AT&T labs will assess
acceptance and test protocols for this equipment on a case-by-case basis.
1) Objective: Prior to entry into AT&T labs, equipment should be compliant to ATT-TP-
76200 Carrier Grade Level 1 requirements, or Non- Carrier Grade Level 1 requirements,
or be Listed (e.g. UL 60950)
2) Requirement: If equipment does not meet the above objective, the manufacturer shall
submit a notarized Letter of Attestation (LOA) that the equipment meets industry
electrical safety, electromagnetic emissions and fire safety standards
NOTE: The above requirements are applicable only for AT&T laboratory testing. All
applicable ATT-TP-76200 and ATT-TP-76450 requirements must be evaluated as in
conformance prior deployment into the network.
Table1.1
Requirements For New Equipment Evaluations
Locations: Carrier Communications space Customer Prem/Partitioned space OSP/Cell Site Class 2-4
Levels: Level 1 Level 3 Level 1 Level 3 Level 1 Level 3
Equipment Types:
Carrier Grade ESR-CG L1 ESR-CG L3 CG L1 + NCG L1 CG L3 + NCG L1 ESR - OSP L1 ESR-OSP L3
Non-Carrier Grade ESR-CG L1 ESR-CG L3 ESR-NCG L1 NCG L3 ESR - OSP L1 ESR-OSP L3
Radio Frequency (RF) ESR-CG L1 ESR-CG L3 ESR-NCG L1 NCG L3 ESR - OSP L1 ESR-OSP L3
Network Admin Support ESR-NCG L1 N/A ESR-NCG L1 N/A N/A N/A
Collocator ESR-CG L1 N/A N/A N/A
N/A N/A
* Note: Less frequent type of evaluations are detailed within this document