Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
3. Acoustic Noise
A. Carrier Grade Equipment
shall meet the acoustic noise requirements as follows:
I. Level 3 -section 4.6 of GR-63-CORE Specifically Table 4-8 for equipment to be
located in an attended room, i.e. 78 LWAd (dB)
II. Level 1:
Option 1 Meet the Level 3 Requirement above
Option 2 - 73 dBA sound pressure, as measured according to ANSI ASA
S12.12.10-2002, or a comparable standard.
B.
OSP/CELL-SITE Equipment shall conform to Section 6.6 of Telcordia GR-3108
Note: Acoustic noise requirements do not apply to either CLECs or to Non Carrier
Grade Level 1 equipment.
4. Electrostatic Discharge (ESD) and Electrical Fast Transients (EFT)
Carrier Grade and OSP/CELL-SITE equipment shall meet the requirements in this
section.
ESD Immunity Criteria
Equipment shall meet the ESD immunity criteria requirements for normal operation and be
tested for installation and repair objectives according to section 2.1.2 (ESD Immunity
Criteria) of Telcordia's GR-1089-CORE, document. All tests shall be conducted as
described in section 2.1.4 of GR-1089 and IEC Publication 61000-4-2.
Special Requirements and Maintenance Information
Any additional equipment-specific requirements in paragraph 2.1.2.4 of GR-1089-CORE
shall be described in the report.
Electrical Fast Transient (EFT)
Equipment shall be tested in accordance with section 2.2 of Telcordia’s GR-1089-CORE,
document with tests conducted as described in section 2.2.1.