Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
Framework and Equipment Requirements
A. Equipment and framework intended for legacy environments of two post
framework lineups:
a. Framework shall be designed for freestanding configuration not requiring
overhead support with maximum height of 7-0”. Framework base shall have
provisions for floor anchoring of anchor hardware up to 18mm diameter and
capabilities for repositioning anchors at minimum of 1” to avoid rebar. AT&T
requirements require all framework to be designed and tested for Zone 4 service.
b. Equipment unit shall be designed for 23 or 19” nominal width mounting and fit
within uprights of a standard 23” width framework. Where 19” equipment is
provided, mounting adapters shall be provided for installation in 23” width
framework. (Limited applications of 19” nominal width framework are used and, if
designated, equipment shall be designed to fit within 17-1/4” clearance between
frame uprights.)
c. Framework should not exceed 2'-6" in overall width.
d. In legacy transport environments equipment and framework should not exceed
15in depth when adding to existing lineups.
e. In newer technology lineups equipment and framework shall not exceed 24” in
depth.
f. Should facilitate a nominal rear aisle of 2’ 6” or greater and a nominal front aisle
of 3’ 0”or greater for equipment installation and maintenance purposes.
g. Where product requires additional cabling space adjacent to equipment
framework, designate on form ESP-001 and/or ESP-002 under Engineering
Data, Additional Space Requirements.
B. Equipment intended for four post framework installation lineups:
A. Framework shall be designed for freestanding configuration not requiring overhead
support with maximum height of 7-0”. Framework base shall have provisions for
floor anchoring of anchor hardware up to 18mm diameter and capabilities for
repositioning anchors at minimum of 1” to avoid rebar. AT&T requirements require
all framework to be designed and tested for Zone 4 service.
B. Equipment unit shall be designed for 23 or 19” nominal width mounting and fit within
uprights of a standard 23” width framework. Where 19” equipment is provided,
mounting adapters shall be provided for installation in 23” width mounting rail
configuration.
C. Framework width shall be designed for maximum 30” width.
D. Framework depth shall be designed for 24” to 36” depth.
Copyright ©2014, AT&T . All Rights Reserved.