Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
7. DC Power
The following requirements are referenced from, but not limited to, the most recent ATIS-
0600315. Test reports showing conformance to all objectives in GR-1089-CORE Section
10 will be accepted as demonstrating conformance to respective requirements in 7.1
through 7.8 of this Section (ATT-TP-76200 Section 7)
All DC powered Carrier Grade network equipment deployed in Network
Equipment Spaces and Outside Plant/Cell Site shall meet the requirements of this
section.
The requirements in this section are for nominal -48 VDC Network Elements
operating in a steady state voltage range of -40 VDC to 56.7 VDC per Table 1 of
ATIS-0600315.
NOTE: AT&T Services may have other DC Power requirements including but not
limited to those referenced in ATT-TP-76450, Telcordia’s GR-499-Core and GR-513-
Core.
Unless otherwise stated, all requirements shall apply to the dc power input terminals of
the telecommunications load equipment. Although systems vary in architecture, all tests
in this standard shall be performed with the minimum number of power supply modules
installed in the system that can be utilized in practice (except for the noise return tests).
For instance if a system has a redundant power supply module(s), all the redundant
supply modules shall be disabled or removed during the tests in this standard (unless
they physically cannot be removed or disabled when the equipment is deployed). In
addition, for systems with multiple feeds such as “A” and “B”, power is only supplied to
one feed during the tests in this standard.
Steady-State Input DC Voltage Requirements
The telecommunications load equipment shall meet its operational requirements at any
input voltage of the correct polarity between and including the minimum and maximum
values specified in Tables 1 in ATIS-0600315.
Undervoltage Requirements
Equipment shall operate properly when exposed to steady state undervoltage conditions
and shall comply with the conformance criteria as described in ATIS-0600315.The
equipment supplier shall provide a report containing the test methods and results for the
above requirement.