Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
Heat Dissipation
A. General Information
AT&T utilizes both the nominal (normal operating) and maximum heat values
(use Watts vs. BTU) for equipment when designing equipment space
infrastructures. The nominal heat value is the primary driver of cooling
requirements. Heat values are documented on the ESP form and, where
required, on the ATIS charts.
ATIS heat reporting charts provide five (5) points of heat. This information
provides a more detailed understanding of the overall equipment cooling
demand.
• Values entered into ESP and ATIS forms may be measured and/or
calculated values.
The configuration of equipment deployed in OSP/CELL-SITE cabinets must be
approved by OSP/CELL-SITE staff prior to approval for use.
B. Level 1 - Compliance Reviews
1. Carrier Grade/Non-Carrier Grade Equipment
a. Equipment shall conform to Telcordia publication GR-63-CORE, Section
4.1.6.
2. Outside Plant/Cell Site Equipment
a. Equipment shall conform to Telcordia publication GR-3108-CORE, Section
4.2.
C. Level 3 - Compliance Reviews
1. Carrier Grade/Non-Carrier Grade Equipment
a. Equipment shall conform to Telcordia publication GR-63-CORE, Section
4.1.6.
b. Manufacturer shall document on ATIS Chart 1 the five (5) equipment heat
levels.
2. Outside Plant/Cell Site Equipment
a. Equipment shall conform to Telcordia publication GR-3108-CORE, Section
4.2.
b. Manufacturer shall document on ATIS Chart 1 the five (5) equipment heat
levels.
D. ESP Form – Heat Dissipation Data Reporting – All Equipment Types/ Review
Levels
1) General
Section 6 heat dissipation results shall be stated on ATT-TP-76200 form ESP-
001 or ESP-002 for individual units and maximum configured systems.
Copyright ©2014, AT&T . All Rights Reserved.