Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
ii. Non Standard – Other than Front to Rear
iii. Multiple-Mixed paths
2. OSP/Cell Site Equipment
a. Manufacturer shall document on the ESP form that the equipment is either:
i. Cooled via electric motor – fan forced, or
ii. Cooled via convection, or
iii. Other
b. Manufacturer shall document on the ESP form that the air flow(s) of the
equipment are:
i. Standard – Front to Rear
ii. Non Standard – Other than Front to Rear
iii. Multiple-Mixed paths
c.
Equipment shall conform to Telcordia publication GR-3108 Section 4.2.1.2
B. Level 3 – Compliance Reviews
1. Carrier Grade Equipment
a. Manufacturer shall document on the ESP form that the equipment is either:
i. Cooled via electric motor – fan forced, or
ii. Cooled via convection, or
iii. Other
b. Manufacturer shall document on the ESP form that the air flow(s) of the
equipment are:
i. Standard – Front to Rear
ii. Non Standard – Other than Front to Rear
iii. Multiple-Mixed paths
c. Equipment shall conform to Telcordia publication GR-63-CORE, Section
4.1.8 inclusive of O4-35 and O4-36
d. Manufacturer shall document on ATIS Chart 2 (see Figure 6.5 below) the
equipment air flow paths and velocity
2. OSP/Cell Site Equipment
a. Manufacturer shall document on the ESP form that the equipment is either:
i. Cooled via electric motor – fan forced, or
ii. Cooled via convection, or
iii. Other
Copyright ©2014, AT&T . All Rights Reserved.
27