ENVIRONMENTAL REQUIREMENTS
Each Port or Expansion
125 Lbs 19”x27”x22”
HEAT DISSIPATION
6800 BTU/HR
Fully Loaded 4-Cabinet
System (requirements
are same for PPN and
EPN)
1700 BTU/HR
Average for a Single
Cabinet
AC POWER REQUIREMENTS
120 volts 50-60Hz
15 Amps
1-Cabinet System
120 volts 50-60Hz Two 15 Amps or 20 Amps
2-Cabinet System
120 volts 50-60Hz Three 15 Amps or 20 Amps
3-Cabinet System
and 15 Amps
120 volts 50-60Hz Two 15 Amps and 20 Amps
4-Cabinet System
or Two 20 Amps
DC POWER REQUIREMENTS
-48 volts 25 Amps Power Source is required for each cabinet
TEMPERATURE/ROOM HUMIDITY RANGE
(Same as multicarrier cabinet)
SHIPPING CARTON DIMENSIONS
AND WEIGHT (Shipped as a single cabinet)
32” x 29.5” x 36”
180 to 200 lbs