ENVIRONMENTAL REQUIREMENTS
ENVIRONMENTAL REQUIREMENTS
(Multicarrier Cabinet)
CABINET
Fully Loaded 5-Carrier (PPN or EPN)
HEAT DISSIPATION
8000 BTU/HR
5000 BTU/HR
AC POWER REQUIREMENTS
120 volts
60Hz
208 volts (3-wire)
60Hz
208/240 volts (4-wire)
60Hz
DC POWER REQUIREMENTS
800 Lbs
70”x32”x28”
Fully Loaded 5-Carrier
Average 5-Carrier
50 Amps MCC
30 Amps MCC
25 Amps MCC
-48 volts
75 Amps
TEMPERATURE/ROOM HUMIDITY RANGE
40° To 120°F.
10% to 95% Relative Humidity at 84°F
10% to 45% Relative Humidity at 110°F
SHIPPING CARTON DIMENSIONS
AND WEIGHT
42” x 32” x 76”
600 to 900 lbs
(Single-Carrier Cabinet)
CABINET
Control - Basic and Duplicated
130 Lbs
20”x27”x22”
Port or Expansion (4 cabinet stack)
500 Lbs 77’’x27”x22”
90